Ethernet/IP (Ethernet/Industrial Protocol) 179
Object model
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
7.3.2.6 Assembly (04
hex
)
Class
Attribute
ID
Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 2 (0x0002)
7.3.2.6.1 Static Assembly Instances
Instance 101 (65
hex
)
Attribute
ID
Access Name Data type Description Default
value
3SetData
ARRAY of BYTE Reference on the process image:
analog and digital output data
-
Instance 102 (66
hex
)
Attribute
ID
Access Name Data type Description Default
value
3SetData
ARRAY of BYTE Reference on the process image:
only digital output data
-
Instance 103 (67
hex
)
Attribute
ID
Access Name Data type Description Default
value
3SetData
ARRAY of BYTE Reference of the process image:
only analog output data
-
Instance 104 (68
hex
)
Attribute
ID
Access Name Data type Description Default
value
3GetData
ARRAY of BYTE Reference of the process image:
analog and digital input data +
Status
-
Instance 105 (69
hex
)
Attribute
ID
Access Name Data type Description Default
value
3GetData
ARRAY of BYTE Reference of the process image:
only digital input data + Status
-