WAGO Modular IO System INTERBUS S Instrukcja Obsługi Strona 137

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 161
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 136
RS232,TTY,RS485 750-650,651,653
:$*2Ç,2Ç6<67(0
11
Structure of the in and output data for Interbus
The module is a combined input and output module with 2 x 16 bit input and output
data.
Outputs:
Word Description
D0 (bit 0-15) Output byte0 Control byte
D1(bit16-31) Output byte2 Output byte1
Inputs:
Word Description
D0 (bit 0-15) Input byte0 Status byte
D1(bit16-31) Input byte2 Input byte1
The RS232 module is also available with a data format of 5 bytes (item-no. 750-
650/000-001).
Outputs:
Word Description
D0 (bit 0-15) Control byte Output byte0
D1(bit16-31) Output byte1 Output byte2
D2(bit32-47) Output byte3 Output byte4
Inputs:
Word Description
D0 (bit 0-15) Status byte Input byte0
D1(bit16-31) Input byte1 Input byte2
D2(bit32-47) Input byte3 Input byte4
Przeglądanie stron 136
1 2 ... 132 133 134 135 136 137 138 139 140 141 142 ... 160 161

Komentarze do niniejszej Instrukcji

Brak uwag