Electronic modules series 750 WAGO
CANopen – 10 kBaud-1 MBaud; digital and analog signals
This eldbus module allows connection
of the AirLINE System as a slave to a
CANopen eldbus. The data is sent
using PDOs and SDOs. The eldbus
module is capable of supporting all bus
modules and automatically creates the
local process image which may include
analog and digital modules.
The local process image is divided
into two data zones containing the
data received and the data to be sent.
The process data can be sent via the
CANopen eldbus to a PLC, PC or NC
for further processing, and received
from the eld via CANopen.
Max. no. of PDOs
5 Tx/5 Rx
No. of available SDOs
1 Tx/1 Rx
Transmission medium
Shielded Cu cable 3 x
0.25 mm2/AWG 23
Max. length of bus line
40 m - 1000 m depends on
Baud rate on the bus cable
Baud rate
10 kBaud - 1 MBaud
Fieldbus module connection
5-pin multi connector series 231
Max. I/O modules per node
64
Digital points per node
256 ls or Os max.
Analog points per node
64 Is or Os max.
Current supply
85 mA typ. 580 mA max.
DeviceNET
TM
– 125-500 kBaud; digital and analog signals
This eldbus module allows connection
of the AirLINE System as a slave to
a DeviceNet eldbus. The eldbus
module is capable of supporting all bus
modules and automatically creates the
local process image which may include
analog and digital modules.
Max. no. of nodes
64 with scanner
Max. no. I/O points
Approx. 6000
(depends on Master)
Transmission medium
Shielded Cu cable
Trunkline
AWG15, 18
(2 x 0.82 mm2 + 2 x 1.7 mm
2
)
Dropline
AWG22, 24 (2 x 0.2 mm2+ 2 x 0.32 mm
2
)
Max. length of bus line
100 m – 500 m (depends on Baud rate on the
bus cable)
Baud rate
125 kBaud , 250 kBaud, 500 kBaud
Fieldbus module connection
1 x Open Style; connection with shielding
Max. I/O modules per node
64
Digital points per node
256 Is or Os max.
Analog points per node
128 Is or Os max.
Current supply
85 mA typ. 580 mA max.
Remote I/O modules (others on request)
Digital input module DI – 2 and 4 channel; high-side switching
The digital input module receives
control signals from digital eld devices
(sensors, etc.). Each input module
has a noise-rejection lter. This lter is
available with different time constants.
An opto-coupler is used for electrical
insulation between the bus and the
eld side.
All digital input modules are
independent of the eldbus and
automatically connected to the next
module when snapped onto the DIN
rail.
No. of inputs
2 or 4
Current consumption
2.5 or 5 mA
(internal)
Signal voltage (0)
-3 V up to +5 V DC
Signal voltage (1)
15 V up to 30 V DC
Input lter
3 ms
Current supply
5 mA typ.
(eld side)
Internal bit width
2 or 4